Series
2100
Flow Monitor
The Data Industrial Series 2100 is
a versatile, compact sized, digital flow monitor. The two line
X 16 character alphanumeric display can be configured by the
user to display flow rate and total simultaneously. Rate or total
may also be displayed with other information such as optional
relay status or control information. The panel meter has a NEMA
4X rated front and conforms to DIN Standard dimensions, 192 mm
X 96 mm, for meter sizes and panel cutouts. Versions of the Series
2100 are also available in NEMA 4 or NEMA 4X wall mount configurations.
Like all Data Industrial flow monitors, the Series 2100 may be field
calibrated by the user. Data Industrial sensors are calibrated by
entering "K" and "offset" numbers, while other
pulse or frequency output sensors may use a "K" factor
only. The Series 2100 also accepts analog, sine wave, a scaled pulse
per gallon signal or a sixteen point linearization equation. Programming
is menu driven. All data is entered using five, front panel mounted
keys. A software lock allows the user to enter a password to prevent
changes in flow total, calibration or control settings. Programming
flexibility is extended to units of measure. Series 2100 software
contains nineteen rate of flow units of measure and seven total flow
units of measure. There is also a provision for adding custom units.
The software contains a self-diagnostic program to assist the operator
in troubleshooting.
| 2100 Series
w/ NEMA 4X Hinged Polymer Enclosure |
 |
The Series 2100 provides a standard
pulse output to interface with external data collection devices
that accept a pulse or dry contact closure. The resolution of
this TTL compatible signal may be programmed from the front keypad.
All calibration information, units of measure and flow totals
are stored in a non-volatile memory that does not require battery
back-up for data retention. The Series 2100 is expandable with
a wide variety of options to customize units for individual requirements.
The Model 2101 is a dual channel version that accepts two flow inputs.
These inputs are independent and need not be the same format. Each
channel can accept a digital pulse, sine wave or analog input. Optional
counters, relays and analog outputs may be assigned to either channel.
The LCD Display may be programmed to show both flow rates, both flow
totals or other combinations. The Model 2101 requires at least one
optional input card for the second channel. If Data Industrial sensors
are used, one connects to the normal sensor input terminals, the
other to a pulse input option card. If two other sensors are used,
two option cards must be used.
Options Include:
| * |
Display backlighting
- with variable contrast for low light situations. |
| * |
Power supplies -
in addition to standard 12 VDC; choose 24 VAC, 12-36 VDC,
115 VAC or 230 VAC. |
| * |
Mechanical counters
- built-in, non-resettable seven digit mechanical counters. |
| * |
Control relays -
Form C mechanical relays, either two or four available, independently
programmed from the keypad by rate for alarms or pump control,
or by total for counting or proportioning. |
| * |
Analog output - isolated
4-20 mA , 0-20 mA, 0-5 Volt or 0-10 Volt outputs, programmed
from the keypad. |
| * |
Analog input - allows
the use of other flow devices with analog outputs. |
| * |
Second flow channel
- converts the 2100 to a 2101, a two channel device. |
| * |
RS232/485 port -
allows two way serial communication with the 2100. |