The Series 310 is a loop
powered, programmable transmitter capable of converting the signal
from Data Industrial flow sensors to a linear 4-20mA analog signal.
In addition to our standard square wave signal, it can also accept
a sine wave making it a versatile transmitter for numerous applications.
Units can be calibrated at our
facility or easily programmed in the field. Field calibration
requires a Data Industrial A310 Programming kit (consisting of
a custom cable and software) and IBM compatible computer running
Windows 3.1® or Windows 9x®. In order to
calibrate, the Model 310 must be connected
to the loop for power, and the A301 cable must be connected to
an available 9-pin COM port on the computer. Once the software is loaded and
communications with the transmitter are established, the following
parameters are entered in the setup screens:
An added feature is a user selectable filter. Set for the minimum (0) the transmitter reacts to actual flow input. Set at the maximum (10) the transmitter provides the greatest dampening possible.
Once the values are set, the "send" command loads the transmitter. All programming can be saved with a file name for later reference.
|